Machine-Tools.Com complete machine and parts directory/newsgroup   >   By Location   >   Oklahoma   >   Fluke 1550 megohmeter used megger

Fluke 1550 megohmeter used megger


Article Sent By: Josefina.hays@machine--tools.com (Josefina Hays)
Josefina Hays is presenting: Fluke 1550 megohmeter used megger
Digital insulation testing up to 5000 Volts
The Fluke 1550 is a digital MegOhmMeter capable of testing switchgear, motors,
generators, and cables at up to 5000 V dc. It can be used for a wide range of
tests including simple spot checks, times tests and breakdown tests. Measurement
storage and PC interface software make it ideal for preventative maintenance.
Short circuit current Greater than 1 mA and less than 2 mA
Insulation test voltage accuracy -0 % to + 10 % at 1 mA load current
Induced ac mains current rejection 2 mA maximum
Charging rate for capacitive load 5 seconds per µF
Leakage current Range: 1 nA to 2 mA
measurement Range: 0.01 µF t 15.00 µF
Accuracy: ± (15 % rdg + 0.03 µF)
Live circuit Indicator Range: 30 V to 600 V ac/dc, 50/60 Hz
Timer 0 to 99 minutes; settable in 1 minute increments; indicated to within 1 second
Ramp 0 % to 100 % of selected test voltage, or until breakdown
(L x W x H) 170 mm x 242 mm x 330 mm
Quicklink 1550B Software Requires a PC running Windows® 95, 98, Me, 2000, NT4.0
Complete specs can be found at
support.fluke.com/find-sales/download/asset/1629685_f_w.pdf
http://us.fluke.com/usen/products/Fluke+1550.htm?Catalog_name=FlukeUnitedStates